Pagina 1 - Troubleshooting Guide

BladeCenter T Type 8720 and 8730Hard ware Maintenance Manual and Troubleshooting Guide 򔻐򗗠򙳰

Pagina 2

viii BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 3

Table 6. Troubleshooting charts Device Suggested action Blade server problem Blade servers turn off for no apparent reason. All blade b

Pagina 4

Table 6. Troubleshooting charts (continued) Device Suggested action “Media not found” error message and other file system error occur o

Pagina 5 - About this manual

Table 6. Troubleshooting charts (continued) Device Suggested action Remote control does not work with default SuSE Linux version 8.0 di

Pagina 6 - Support telephone numbers

Table 6. Troubleshooting charts (continued) Device Suggested action CD-ROM drive is not recognized after being switched back to blade s

Pagina 7 - Contents

Table 6. Troubleshooting charts (continued) Device Suggested action Ethernet disconnect notice will not appear when running Windows 2000.

Pagina 8

Table 6. Troubleshooting charts (continued) Device Suggested action Pressing F1 brings up browser help instead of performing BladeCenter

Pagina 9 - Contents vii

Table 6. Troubleshooting charts (continued) Device Suggested action The monitor displays video for blade server 8 during management modu

Pagina 10

Table 6. Troubleshooting charts (continued) Device Suggested action Mouse is not detected during SuSE installation. The installation of

Pagina 11

Table 6. Troubleshooting charts (continued) Device Suggested action Updating the switch-module configuration through the switch does not

Pagina 12 - Serial number label

Table 7. Light path diagnostics (continued) Lit LED Cause Action Critical error A critical system error has occurred, such as nonredu

Pagina 13 - Related publications

Chapter 1. General information The IBM® BladeCenter®T Types 8720 and 8730 units are rack-mounted, high-density, high-performance blade s

Pagina 14

Temperature error messages Note: See Chapter 7, “Parts listing, BladeCenter T Type 8720 and 8730,” on page 107 to determine which

Pagina 15

Note: See Chapter 7, “Parts listing, BladeCenter T Type 8720 and 8730,” on page 107 to determine which components should be replac

Pagina 16

Note: See Chapter 7, “Parts listing, BladeCenter T Type 8720 and 8730,” on page 107 to determine which components should be replac

Pagina 17

Note: See Chapter 7, “Parts listing, BladeCenter T Type 8720 and 8730,” on page 107 to determine which components should be replac

Pagina 18

Bus error messages Note: See Chapter 7, “Parts listing, BladeCenter T Type 8720 and 8730,” on page 107 to determine which componen

Pagina 19 - Front view

3. Damaged data in BIOS code can cause undetermined problems. Check the LEDs on all the power supplies. If the LEDs indicate th

Pagina 20 - System service cards

v Operating system software — type and version levelNote: To eliminate confusion, identical systems are considered identical only

Pagina 21 - Media tray

Chapter 7. Parts listing, BladeCenter T Type 8720 and 8730 This parts listing supports the Eserver BladeCenter T Type 8720 and 873

Pagina 22

Index System (Eserver BladeCenter T Type 8720 and 8730) FRU No. CRU/FRU 2-Post rack mount kit (8720 model 1Rx) 90P3802 FRU 2-Post

Pagina 23 - Power modules

Index System (Eserver BladeCenter T Type 8720 and 8730) FRU No. CRU/FRU 1 Switch filler (model 2Rx) 39M3261 CRU 2 Blower module (m

Pagina 24

Record information about your BladeCenter T unit in the following table. You will need this information when you register your Blad

Pagina 25 - Rear view

110 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 26

Appendix A. Getting help and technical assistance If you need help, service, or technical assistance or just want more information a

Pagina 27

can create a customized support page. The support page has many sources of information and ways for you to solve problems, includi

Pagina 28

Appendix B. Related service information Note: The service procedures are designed to help you isolate problems. They are written wit

Pagina 29 - I/O modules

Electrical safety CAUTION: Electrical current from power, telephone, and communication cables can be hazardous. To avoid personal inj

Pagina 30

v Do not use worn or broken tools and testers. v Never assume that power has been disconnected from a circuit. First, check

Pagina 31

3. Check the power cord for: a. A third-wire ground connector in good condition. Use a meter to measure third-wire ground conti

Pagina 32

Grounding requirements Electrical grounding of the computer is required for operator safety and correct system function. Proper groundi

Pagina 33

Statement 1 DANGER Electrical current from power, telephone and communication cables is hazardous. To avoid a shock hazard: v D

Pagina 34

Statement 2 CAUTION: When replacing the lithium battery, use only IBM Part Number 33F8354 or an equivalent type battery recommended

Pagina 35 - Cabling the Ethernet port

UserlabelCMM1CMM2Important: Do not place the label on the blade server itself or in any way block the ventilation holes on the bla

Pagina 36

Statement 4 ≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs) CAUTION: Use safe practices when lifting. Statement 5

Pagina 37

Statement 20 CAUTION: To avoid personal injury, before lifting the unit, remove all the blades to reduce the weight. Statement 21

Pagina 38

Instrução 1 PERIGO A corrente elétrica proveniente de cabos de alimentação, de telefone e de comunicações é perigosa. Para evitar

Pagina 39 - What to configure

Instrução 2 CUIDADO: Ao substituir a bateria de lítio, utilize apenas uma bateria IBM, Número de Peça 33F8354 ou uma bateria de

Pagina 40

Instrução 4 ≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs) CUIDADO: Ao levantar a máquina, faça-o com segurança. In

Pagina 41

Instrução 20 CUIDADO: Para prevenir acidentes, antes de erguer a unidade, remova todas as láminas para reduzir o peso. Instrução 21

Pagina 42

126 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 43 - Using IBM Director

Laser Klass 1. Appendix B. Related service information 127

Pagina 44

128 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 45 - Chapter 3. Diagnostics

Appendix B. Related service information 129

Pagina 46

Notices and statements used in this book The caution and danger statements that appear in this book are also in the multilingual S

Pagina 47 - Installation guidelines

130 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 48 - Type 8720 (dc power)

Appendix B. Related service information 131

Pagina 49 - Type 8730 (ac power)

Luokan 1 Laserlaite 132 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 50 - ESD connector

Important: Toutes les consignes Attention et Danger indiquées dans la bibliothèque IBM documentation sont précédées d’un numéro. Ce de

Pagina 51

Notice n° 1 DANGER Le courant électrique passant dans les câbles de communication, ou les cordons téléphoniques et d’alimentation

Pagina 52 - Preinstallation steps

Notice n° 2 ATTENTION: Remplacez la pile au lithium usagée par une pile de référence identique exclusivement - voir la référence

Pagina 53

≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs) ATTENTION: Faites-vous aider pour soulever ce produit. Notice n° 5 ATTE

Pagina 54 - Retainer

ATTENTION: Pour éviter tout risque de blessure, retirez tous les Serveurs lame de l’unité avant de la soulever. Notice n° 21 AT

Pagina 55

Hinweis 1 VORSICHT Elektrische Spannungen von Netz-, Telefon- und Datenübertragungsleitungen sind gefährlich. Aus Sicherheitsgründen: v

Pagina 56

Hinweis 2 ACHTUNG: Eine verbrauchte Batterie nur durch eine Batterie mit der IBM Teilenummer 33F8354 oder durch eine vom Hersteller

Pagina 57 - Removing a power module

Features and specifications for the BladeCenter T Type 8720 unit The following table provides a summary of the features and specifi

Pagina 58 - Installing a power module

Hinweis 4 ≥18 kg ≥32 kg ≥55 kg ACHTUNG: Beim Anheben der Maschine die vorgeschriebenen Sicherheitsbestimmungen beachten. Hinwei

Pagina 59

Hinweis 20 ACHTUNG: Um Verletzungen zu vermeiden, entfernen Sie vor dem Anheben der Einheit zur Verringerung des Gewichts alle Blad

Pagina 60 - Installing the media tray

Avviso 1 PERICOLO La corrente elettrica circolante nei cavi di alimentazione, del telefono e di segnale è pericolosa. Per evitare

Pagina 61 - Serial port

Avviso 2 ATTENZIONE: Quando si sostituisce la batteria al litio, utilizzare solo una batteria IBM con numero parte 33F8354 o batte

Pagina 62

Avviso 4 ≥18 kg ≥32 kg ≥55 kg ATTENZIONE: Durante il sollevamento della macchina seguire delle norme di sicurezza. Avviso 5

Pagina 63

Avviso 20 ATTENZIONE: Per evitare incidenti, prima di sollevare l’unità, rimuovere tutte le lame in modo da ridurre il peso. Avviso

Pagina 64 - Power LED

146 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 65 - Removing a blower module

Appendix B. Related service information 147

Pagina 66 - LAN module

148 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 67 - Thumbscrew Thumbscrew

Appendix B. Related service information 149

Pagina 68

Notes: 1. For details about the BladeCenter T unit port specifications, see “BladeCenter T unit power, controls, and indicators” o

Pagina 69 - Installing the LAN module

150 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 70

Importante: Todas las declaraciones de precauciín de esta IBM documentation empiezan con un número. Dicho número se emplea para estab

Pagina 71

Declaración 1 PELIGRO La corriente eléctrica de los cables telefínicos, de alimentaciín y de comunicaciones es perjudicial. Para evitar

Pagina 72 - Installing an I/O module

Declaración 2 PRECAUCIÓN: Cuando desee sustituir la batería de litio, utilice únicamente el número de pieza 33F8354 de IBM o cualq

Pagina 73 - Blade servers

≥18 kg ≥32 kg ≥55 kg PRECAUCIÓN: Tome medidas de seguridad al levantar el producto. Declaración 5 PRECAUCIÓN: El botín de cont

Pagina 74 - Filler blade

PRECAUCIÓN: Para prevenir ferimentos pessoais, antes de levantar a unidade retire todas as låminas para diminuir o peso. Declaración 2

Pagina 75 - Installing a blade server

156 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 76 - Removing a blade server

Appendix C. Notices This information was developed for products and services offered in the U.S.A. IBM may not offer the products,

Pagina 77

Trademarks The following terms are trademarks of International Business Machines Corporation in the United States, other countries, or

Pagina 78 - Captive fasteners (2)

When referring to processor storage, real and virtual storage, or channel volume, KB stands for approximately 1000 bytes, MB stands

Pagina 79 - AC rear panel

Features and specifications for the BladeCenter T Type 8730 unit The following table provides a summary of the features and specifi

Pagina 80 - Captive fasteners (3)

Electronic emission notices Federal Communications Commission (FCC) statement Note: This equipment has been tested and found to comply

Pagina 81

European Union EMC Directive conformance statement This product is in conformity with the protection requirements of EU Council Direct

Pagina 82 - Captive fasteners

Power cords For your safety, IBM provides a power cord with a grounded attachment plug to use with this IBM product. To avoid ele

Pagina 83 - Lower flex circuit assembly

IBM power cord part number Used in these countries and regions 14F0033 Abu Dhabi, Bahrain, Botswana, Brunei Darussalam, Channel Island

Pagina 84

164 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 85

Index Aac power LED 13 acoustical noise emissions 5, 7 Bbezelinstalling 45 removing 45 bezel assemblyinstalling 44 removing 43 removing a

Pagina 86 - (DC shown)

II/O module 60 configuring 29 installing 62 removing 62 types 60 installationcompleting 66 guidelines 37 installingair filter 44 bezel 45 b

Pagina 87

modules (continued)management 51 media tray 49 mouse connector 17 Nnetworkconnecting 25 networking guidelines 31 notes, important 158 notic

Pagina 88 - Captive fastener (4)

Ttelco alarms connector 18 temperature 5, 7 trademarks 158 troubleshootingcharts 89 UUnited States electronic emission Class A notice 16

Pagina 90 - Screw (6)

Notes: 1. For details about the BladeCenter T unit port specifications, see “BladeCenter T unit power, controls, and indicators” o

Pagina 91 - Backplane insulator

򔻐򗗠򙳰Part Number: 25K8107 (1P) P/N: 25K8107

Pagina 92 - Air damper

Major components of the BladeCenter T Types 8720 and 8730 unit The following illustration shows the locations of major components i

Pagina 94 - Slight angle toward

System service cards These cards contain system service instructions and a writable area for your use. The cards are located in a

Pagina 95 - Mechanical chassis

v Error: When this amber LED is lit, it indicates that an error has been detected somewhere on the management module. When this

Pagina 96 - Mechanical chassis

System status LEDs: The LEDs on this part of the panel provide status information for the BladeCenter T unit. v Power: When cont

Pagina 97

Power modules AC in LEDDC out LEDDC in LEDError LEDAC power module DC power moduleDC out LEDError LED Power module LEDs: Each power module ha

Pagina 98

Table 3. Power module LEDs (continued) DC IN or AC IN DC OUT ! (Error) (amber) Description and action Off Off Off or On* There is

Pagina 99 - Error symptoms

Rear view This section identifies the components and indicators on the rear of the BladeCenter T unit. I/O module 2 I/O module 1I/O modu

Pagina 100

KVM (keyboard, video, mouse) module indicators and input/output connectors The KVM module is a hot-swap module that is installed on

Pagina 101

Connectors: The KVM module has the following I/O connectors: v Keyboard connector: The BladeCenter T KVM module contains one PS/2-

Pagina 102

LAN-module indicators and input/output connectors The LAN module is a hot-swap module that is installed on the rear of the BladeCent

Pagina 103

Note: The service processor, management module, or systems-management function must monitor the alarm reset inputs to maintain the f

Pagina 104

BladeCenter T Type 8720 and 8730Hard ware Maintenance Manual and Troubleshooting Guide 򔻐򗗠򙳰

Pagina 105

2. Reinstall the four blowers into the rear of the BladeCenter T unit if you have not done so already. See “Removing and insta

Pagina 106

Notes: 1. Within 2 minutes after power has been connected to the BladeCenter T unit, the management module applies power to the

Pagina 107 - problems occur

breakers to the Off position or removing the fuses as applicable. Make sure that both circuits are disconnected or turned off. If

Pagina 108

Chapter 2. Configuring the BladeCenter T unit The BladeCenter T unit automatically detects the modules and blade servers that are in

Pagina 109

For best results when using the Web browser, set the monitor to 256 colors. Use only the video resolutions and refresh rates give

Pagina 110 - Power error messages

Setting up the remote connection To configure and manage the BladeCenter T unit and blade servers, you must first set up the remot

Pagina 111

Complete the following steps to connect the Ethernet cable to the management module. 1. Connect one end of a Category 5 or highe

Pagina 112 - Switch error messages

Starting the management and configuration program Complete the following steps to start the management and configuration program: 1.

Pagina 113

Setting management and configuration program options From the management and configuration program main menu, you can select settings

Pagina 114 - Undetermined problems

module automatically when needed). Otherwise, configure the DHCP setting as you prefer. You must configure the static IP address onl

Pagina 115 - Problem determination tips

Note Before using this information and the product it supports, be sure to read Appendix C, “Notices,” on page 157.Sixth Edition (

Pagina 116

and remote management station. This is in addition to the IP addresses that are configured on the management module. You might als

Pagina 117

must be installed in the BladeCenter T unit in I/O-module bay 1 or 2, or both, before the integrated Ethernet controllers on each

Pagina 118

A typical, preferred BladeCenter T network topology is shown in the following illustration. See the IBM Eserver BladeCenter T Planni

Pagina 119

3. Avoid network configurations that could lead to data loops, if possible. Loops will be created if you connect multiple ports

Pagina 120

Director software can automatically discover the BladeCenter T unit (out-of-band, using the Ethernet port on the management module) a

Pagina 121 - Using the documentation

Chapter 3. Diagnostics This section provides basic troubleshooting information to help you resolve some common problems that might occ

Pagina 122

For example: A system error has occurred, and you have noted that the BladeCenter T system-error LED is lit on the system LED pan

Pagina 123 - General safety

Chapter 4. Setting up the BladeCenter T hardware This chapter provides instructions for setting up the BladeCenter T unit and instal

Pagina 124 - Electrical safety

Before you begin to install options in the BladeCenter T unit, read the following information: v Read the safety information begin

Pagina 125 - Safety inspection guide

(see the documentation that comes with your blade server for information about turning on the blade server). Make sure that you sh

Pagina 126

About this manual This manual contains diagnostic information, a Symptom-to-FRU index, service information, error codes, error messages,

Pagina 127 - Grounding requirements

Handling static-sensitive devices Attention: Static electricity can damage electronic devices and your system. To avoid damage, keep

Pagina 128

v Limit your movement. Movement can cause static electricity to build up around you. v Handle the device carefully, holding it

Pagina 129

Preinstallation steps Before you begin, read the documentation that comes with your module or option. Statement 8: CAUTION: Never r

Pagina 130

Removing and installing the bezel assembly The BladeCenter T unit comes with a bezel assembly containing a removable and replaceable

Pagina 131

Installing the bezel assembly Complete the following steps if you are installing the bezel assembly at the front of the BladeCenter

Pagina 132

1. Remove the bezel from the front of the BladeCenter T unit (see “Removing the bezel assembly” on page 43 for instructions). 2.

Pagina 133

Removing and installing power modules The BladeCenter T unit is separated into two power domains. To support devices in power domain

Pagina 134

Power module 1Power module 2CMM1CMM2Power module 3ESDPower module 4Release handleFiller moduleRelease buttonRemoving a power module Complete the

Pagina 135

2. Grip the power-module handle with one hand and slowly pull the power module out of the bay. Use your other hand to support

Pagina 136

Removing and installing the media tray The media tray is a hot-swap unit that is installed in the front of the BladeCenter T unit

Pagina 137 - Laser Klass 1

Lea atentamente todas las declaraciones de precaución y peligro ante de llevar a cabo cualquier operación. Online support You can dow

Pagina 138

Removing the media tray Complete the following steps to remove the media tray in the front of the BladeCenter T unit: 1. Open th

Pagina 139

Removing and installing management modules The BladeCenter T unit comes with one hot-swap management module in management-module bay 1

Pagina 140

CMM1CMM2ESDRelease latchManagement moduleRemoving a management module Notes: 1. If you are removing the only management module in the

Pagina 141

Installing a management module Complete the following steps to install a management module in the BladeCenter T unit: 1. If you a

Pagina 142 - Luokan 1 Laserlaite

Removing and installing blower modules The BladeCenter T unit comes with four hot-swap blowers for cooling redundancy. The blowers ar

Pagina 143

2413Release latch(open)Error LEDPower LEDRemoving a blower module Use the following instructions to remove a blower at the rear of the

Pagina 144

Removing and installing the KVM (keyboard, video, mouse) module The KVM module is a hot-swap unit that is installed in the rear o

Pagina 145

Removing the KVM module Complete the following steps to remove the KVM module at the rear of the BladeCenter T unit. 1. Remove t

Pagina 146

Removing and installing the LAN module The LAN module is a hot-swap unit that is installed in the rear of the BladeCenter T unit

Pagina 147

Removing the LAN module Complete the following steps to remove a LAN module from the rear of the BladeCenter T unit: 1. Fully lo

Pagina 148

Contents About this manual . . . . . . . . . . . . . . . . . . . . . . . iii Important safety information . . . . .

Pagina 149

Removing and installing I/O modules For blade server communication with the network, the BladeCenter T unit supports up to four hot-

Pagina 150 - ≥18 kg ≥32 kg ≥55 kg

Table 5. Hot-swap I/O module types by location for redundancy (continued) Bays I/O-module function Permissible I/O module 3 and 4 Ne

Pagina 151

Releaselatch(open)Releaselatch(open)EthernetswitchmoduleFibreChannelswitchmoduleFillermoduleFillermoduleRemoving an I/O module Use the following

Pagina 152

Blade servers The BladeCenter T unit supports up to eight high-performance blade servers. Each blade server is an enclosure that con

Pagina 153

Removing and installing a blade server or filler module Use the instructions in this section to remove or install a blade server

Pagina 154

Installing a blade server Complete the following steps to install a blade server or filler blade in the BladeCenter T unit. Stateme

Pagina 155

10. If you have other modules to install at the front of the unit, do so now. Otherwise reinstall the bezel assembly on the f

Pagina 156

Chapter 5. Service replaceable units This chapter describes the removal of server components. Important: The field replaceable unit (

Pagina 157

DC terminal cover with fasteners Complete the following steps to replace the dc terminal cover on the Type 8720 unit. Note: v Re

Pagina 158

AC rear panel Complete the following steps to replace the ac rear panel located at the rear of the unit. Note: v Read “Installa

Pagina 159

Removing the media tray . . . . . . . . . . . . . . . . . . . .50 Installing the media tray . . . . . . . . . .

Pagina 160

10. If you have no other replacement procedures to perform at the rear of the system, re-install the LAN module (see “Installing

Pagina 161

9. Position the new dc rear panel so that it aligns with the dc power terminals on the system. Make sure that the dc rear pa

Pagina 162

Upper flex circuit assemblyCaptive fasteners7. Carefully remove the old upper flex circuit assembly by placing your fingers under the

Pagina 163

2. For Type 8720 systems, remove the dc terminal covers and power connections to each of the dc terminals. For Type 8730 system

Pagina 164

17. Start up the system (see “Starting the BladeCenter T unit” on page 19). 74 BladeCenter T Type 8720 and 8730: Hardware Main

Pagina 165

Docking board/blower housing assembly - (dc Type 8720 and ac Type 8730) Complete the following steps to replace the docking board/bl

Pagina 166

Docking board/blowerhousing assembly(DC shown)12. Grab the housing by the housing frame above and below the power inlet receptacles, a

Pagina 167 - Appendix C. Notices

Rear chassis stiffener bracket Complete the following steps to replace the rear chassis stiffner bracket. Note: v Read “Installatio

Pagina 168 - Important notes

UPChassis stiffener bracketCaptive fastener (4)UP10. Pull the old rear chassis stiffner bracket off the chassis. 11. Remove the new

Pagina 169 - Battery return program

Backplane Complete the following steps to replace the backplane in your BladeCenter T unit Note: v Read “Installation guidelines”

Pagina 170

Getting help and information from the World Wide Web . . . . . . . . . 111 Software service and support . . . . . . . .

Pagina 171 - Appendix C. Notices 161

15. Loosen and remove the six non-captive screws that mount the old backplane to the chassis. Backplane insulatorBackplaneScrew (6)

Pagina 172 - Power cords

Backplane insulator Complete the following steps to replace the backplane insulator. Note: v Read “Installation guidelines” on page

Pagina 173 - Appendix C. Notices 163

v Reinstall the LAN module (see “Installing the LAN module” on page 59). v Reinstall the KVM module (see “Installing the KVM

Pagina 174

Spring7. Use tape to hold the air dampers above and below the empty air damper slot in the open position. This will provide mo

Pagina 175

Slight angle towardthe rear of the system11. Hold the air damper angled slightly towards the back of the server; then, pull the air

Pagina 176

Mechanical chassis Complete the following steps to replace the mechanical chassis of the BladeCenter T system. Note: v Read “Instal

Pagina 177 - Index 167

19. Holding the backplane at the top near the guide pins, pull the backplane out and off of the guide pins. 20. Remove the b

Pagina 178

35. Install the management module(s) at the front of the unit (see “Installing a management module” on page 53). 36. Install th

Pagina 179

88 BladeCenter T Type 8720 and 8730: Hardware Maintenance Manual and Troubleshooting Guide

Pagina 180 - (1P) P/N: 25K8107

Chapter 6. Symptom-to-FRU index This index supports the Eserver BladeCenter T Type 8720 and 8730 systems. Notes: 1. Check the conf