Ha rdw ar e M ain tenan ce Man u alIBMPCServer/EnterpriseRacksTypes 9306, 9308
viii Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
to install later in this procedure.Cable coverScrewSlotTab5. Ensure that the keyboard and mouse cable is routed through the slots on thebottom of the
Note: When the keyboard is installed correctly, it will sit flat inside of the trayand not extend above or below the 1U height of the tray.8. Route th
11. Loosen the four rail-adjustment screws on both rear slide-rail brackets; then,extend the brackets to their maximum outward adjustment.Note: You mu
14. Adjust the rear slide-rail brackets to fit the depth of your rack cabinet; then,attach the brackets to the rack cabinet using four screws from the
16. To attach the front of the tray to the rack cabinet, pull the tray halfway out ofthe rack cabinet so that you can access the front of the rails; t
Installing an optional console switchYou can use a console switch to attach more than one server to a single monitorand space-saver keyboard. The cons
that you can move the power supply over a short distance.Power supplyPower supplystorage bracket3. To remove the power supply storage bracket from the
4. Install the console switch behind the flat panel monitor and keyboard tray usingtwo screws from the miscellaneous hardware kit.81A2345671A2Consoles
98 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Parts listing (Type 9306 Model OPT)12231U Flat Panel Monitor Console Kit 99
General CheckoutUse the following procedure for diagnosing keyboard, mouse, and video problemsfor the IBM PC Server Rack Enclosure and the IBM Rack en
Index Rack Enclosure (Type 9306 Model OPT) FRU1 1U Rack Mount Monitor without Keyboard (Optional) 32P10982 Slides, with Mounting Bracket (Optional) 32
Installing Optional DevicesThere are many servers and optional devices that you can install in your NetBAY25or NetBAY42 Rack cabinet. Always read the
Installing devices on the rack cabinet mounting flangesWhen you install optional devices in the rack cabinet, secure the device on rackmounting flange
DANGERElectrical current from power, telephone, and communication cables ishazardous.To avoid a shock hazard:v Do not connect or disconnect any cables
Statement 6:CAUTION:Do not place any object on top of a rack-mounted device unless thatrack-mounted device is intended for use as a shelf.Installing t
2. From the inside of the rack mounting flange, insert one edge of the cage nutinto the hole.3. Push the tool through the hole and hook the other edge
Installing an uninterruptible power supplyThe uninterruptible power supply (UPS) comes with standard rack mountingbrackets installed and can occupy ei
Rear of railUPSUPSscrewsFront of railFigure 28. Installing a UPSInstalling Optional Devices 107
1. Use the template that comes with the UPS to determine where to install clipnuts that come with the UPS.2. If you are installing rails, do the follo
Power Distribution UnitNote: For information and installation instructions for the IBM NetBAY Rack PowerDistribution Units, see “Installing Optional D
a. Device extender cable (connects between the device and the serverselector unit)b. Failing devicec. Server selector cable (connects between the serv
Note: There are two types of Power distribution units available:v High voltagev Low voltageInstalling a PDU verticallyUse the following general proced
2. Attach PDUs to the vertical mounting plate that comes with the PDU.3. Install the vertical mounting plate in the side of your rack cabinet with the
Installing a large serverUse the following general procedure to install a PDU horizontally in a rack cabinet:Server handlesServer rail screwsCable-man
1. See the server documentation for detailed installation information.2. Use the template and rack mounting instructions that come with your server to
Installing a storage expansion unitStorage expansion units install on fixed rails in your rack cabinet and occupy 3U ofrack mounting space. See the do
Installing a Fibre Channel RAID controller unitThe Fibre Channel RAID controller unit installs on fixed rails in the rack cabinet andoccupies 4U of ra
1. See the hub documentation for detailed installation information.2. Attach the hub to its mounting tray with the four screws provided.3. Install the
1. See the switch documentation for detailed installation information.2. Attach the rails to the front and rear of the rack, adjusting the length of t
1. Determine the location for the fixed shelf within the rack cabinet.2. Attach the shelf brackets that come with the rack cabinet to the rear of the
Installing a keyboard trayThe keyboard tray can hold a standard keyboard or a space-saver keyboard, andoccupies 1U of space in your rack cabinet. With
Powering off the rackBefore performing service on the rack, follow this procedure to prevent personalinjury and to avoid damaging the rack and the ins
1. Ensure that a keyboard tray is properly installed in your rack cabinet (see“Installing a keyboard tray” on page 119) with at least 2U of clearance
See the documentation that comes with your monitor shelf for detailed installationinstructions. Use the following general procedure to install a monit
You can install a console switch inside the rear storage compartment NetBAYmonitor shelf, vertically in the side of your rack cabinet, or horizontally
another console switch in a tiered configuration. Console cable sets areavailable in different lengths, and are color-coded the same as the ports onth
The NetBAY Console Cable Set is available separately to connect servers to yourconsole switch. The console cables are available in different lengths,
Installation overviewUse the following general steps to install your console switch:1. Install the console switch in your rack cabinet:v Install a con
to attach the console switch to the side braces.Continue with the rest of the procedure to cable your console switch.Note: Refer to the Apex User Guid
5. Route your mouse cable neatly toward the rear of the console switch; then,connect it to the appropriate mouse connector on Port A of the console sw
Installing a console switch horizontally in a rackUse the following procedure to install the console switch horizontally in 1U of EIArack mounting spa
either cage nuts or clip nuts.ImportantInformationImportantInformation101015A263744Continue with the rest of the procedure to cable your console switc
4 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
9. Connect one end of a console cable set to one of the numbered ports on therear of the console switch.10. Route the console cable set toward the rea
power outlets.Notes:1. Power cables for devices that you will connect to the Rack PDU do not comewith the Rack PDU.2. You will have some unused parts
v Install devices vertically in the side of your rack cabinet according to“Installing devices vertically” on page 156, ORv Install a single device hor
4. If you have a second M/PDU device to install, install it on the vertical mountingplate with four M3x5 screws that come with the second device.5. In
Notes:a. Removing the rack doors and side panels might make your Rack PDUinstallation easier.b. Use clip nuts for rack cabinets with round holes; use
6. Install the 1U blank filler panel 1 on the front of the rack cabinet at the sameU level as the Rack PDU. Use two M6 screws that come with this op
2. Verify that the circuit breaker switch is in the Off position before installing yourRack PDU.3. Attach a dual-device attachment bracket 6 to the
rear of the rack cabinet with four M6 screws and clip nuts or cage nuts (twoscrews and nuts per bracket).7. Install the 1U blank filler panel 1on th
Statement 1:CAUTION:To ensure safety, all configurations of the rack cabinet must be certified by anationally recognized testing laboratory in order t
2. Reinstall the screw on the cable clamp 1 and repeat step 1 for the otherdevice if you installed two devices.3. Route the line cords down and towa
Type 9306 Model 250/420/421FeaturesThe IBM NetBAY 42, Type 9306, Model 420 with side panels, Model 421 withoutside panels and the IBM NetBAY 25, Type
Cabling instructions for horizontal-mount PDUsIf your Rack PDU came with more than one line cord, select either the high-voltagecord or the low-voltag
Reinstall the screw on the cable clamp and repeat this step for the other device,if you installed two devices.2. Route the line cords left or right, t
77Figure 53. Connecting and routing other power cables to the outlets142 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Rack PDU specificationsWhen connected to a dedicated power source, the Rack PDU conforms to UL950,CSA 22.0-950, EN-60950, and IEC-950 standards. The f
Power cablesPower cables that you use to connect a system, storage expansion unit, and otherdevices to the Rack PDU usually come with those devices. T
Line cordsA 4.3 m (14 ft) country-specific line cord that you use to connect your Rack PDU toa properly wired, grounded, and dedicated power source co
You must install the Rack PDU vertically in the side of your rack cabinet with theprovided mounting hardware. The following parts come with the Rack P
Statement 1:DANGERElectrical current from power, telephone, and communication cables ishazardous. To avoid a shock hazard:v Do not connect or disconne
3. Install the vertical mounting plate in the side of your rack cabinet with four M6screws and nuts that come with this option. Make sure that the thr
5. Route the line cord towards a dedicated power source. Use the provided cablestraps to secure the line cord along the way. Use the openings in your
Note: The illustrations in this documentation might be slightly different from yourhardware.Installing a rack cabinetThe NetBAY25 Rack cabinet is a 25
Statement 1:DANGERElectrical current from power, telephone, and communication cables ishazardous. To avoid a shock hazard:v Do not connect or disconne
3. If you have a second M/PDU device to install, install it on the vertical mountingplate with four M3x5 screws that come with the second device.4. In
5. Install the cable-management bracket 1 beside the vertical mounting platewith four M6 screws and nuts that come with this option.6. Route the fix
7. Route each line cord towards a dedicated power source. Use the provided cablestraps to secure the line cords along the way. Use the openings in you
Rack PDU specificationsWhen connected to a properly wired, grounded, and dedicated power source, theRack PDU conforms to UL950, CSA 22.0-950, EN-60950
Line cordsThe 2.5 m (8.2 ft) fixed line cord on the Rack PDU determines the connectivity ofthe Rack PDU. The following table contains a list of the li
You can install the Rack PDU vertically in the side of your rack cabinet, orhorizontally within 1U of EIA mounting space in your rack cabinet. The mou
1. Refer to the documentation that comes with your rack cabinet for additionalinformation.Note: Removing the rack doors and side panels might make you
5. Install the cable-management bracket 1 beside the vertical mounting plate withfour M6 screws and nuts that come with this option.Proceed to “Cablin
2. Install the horizontal mounting bracket 3 on one side of the Rack PDU 5with M3x5 screws 4.Note: There are two sets of mounting holes on the b
Expansion NetBAY42 Rack cabinets do not come with side panels, but do includethe required hardware for building a suite of rack cabinets. The rack cab
5. Install the 1U blank filler panel 1 on the front of the rack cabinet at the sameU level as the Rack PDU. Use two M6 screws that come with this op
3. Push the two Rack PDUs together, aligning the holes on the dual-deviceattachment brackets; then, use four M6 screws to secure the front 1 and rea
6. Install the 1U blank filler panel 1 on the front of the rack cabinet at the sameU level as the Rack PDU. Use two M6 screws that come with this op
Statement 1:DANGERElectrical current from power, telephone, and communication cables ishazardous. To avoid a shock hazard:v Do not connect or disconne
The power control button on the device and the power switch on the powersupply do not turn off the electrical current supplied to the device. The devi
5. Route each line cord towards a dedicated independent power source, such as aUPS or electrical outlet. Use the provided cable straps to secure the l
2. Connect the other line cord to the Backup inlet on the Rack PDU. Use the linecord that you will connect to your backup power source.3. Remove the s
Figure 72. Connecting and routing other power cables to the outletsInstalling Optional Devices 167
Rack PDU specificationsWhen connected to a dedicated power source, the Rack PDU conforms to UL950,CSA 22.0-950, EN-60950, and IEC-950 standards. The f
Power cablesPower cables that you use to connect a server (with more than one power supply)to the Rack PDU usually come with the server. The following
Figure 3. Primary NetBAY42 Rack cabinet with side panels8 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Line cordsTwo 4.3 m (14 ft) country-specific line cords that you use to connect your RackPDU to properly wired, grounded, and dedicated power sources
OneKMThreeKMKMTwoAux.ResetImportantInformation10ThreeKMKMTwoThreeKMThreeKMKMTwoFigure 73. Selector switch in monitor compartmentFRONTREAROneKMThreeKMK
Selector switch cable connectionsOneKMThreeKMKMKMTwoAux.ResetImportantInformation10Power CordConnectorPowerSwitchComputer 3MouseComputer 3KeyboardComp
Selector switch environmentResetting the selector switchThe selector switch can be reset by depressing the Reset button on the back panelof the select
Blank bezelFixed shelf174 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Keyboard trayTo remove the tray from the side rails, pull up on the left rail tab and push down onthe right rail tab.Removing the existing flat panel
Note: Even though this hinge cover is not used with the Flat Panel MonitorRack Mount Kit, do not discard it. Store it with the other monitor standpart
Note: The Flat Panel Monitor Rack Mount Kit and keyboard tray require 3U of rackmounting space. If the keyboard tray does not have at least 2U of clea
You have now finished attaching the flat panel monitor to its stand. The rest ofthe installation process involves preparing the keyboard tray for stor
Note: Clean the installation area on the keyboard tray with a suitable cleaningagent, such as alcohol, before installing the rubber bumpers on the fro
Figure 4. Expansion NetBAY42 Rack cabinet without side panelsType 9306 Model 250/420/421 9
8. Connect the power supply to the monitor and route the cable under the tabnear the top of the monitor stand 1; then, secure the power cable with t
13. Fold the flat panel monitor down until it rests on the rubber bumpers; then,gently push back and remove the small cable exit cover 1 on the moni
Configuring the selector switchNote: For information about the IBM NetBAY Console Switch, see “IBM NetBAYConsole Switch” on page 121.Note: Some select
Type of Symbol Symbol MeaningPlus + Server connected and runningAsterisk * Secondary selector switch connected and runningAdvanced selector switch fun
– Enabled or disabled– Typematic rate– LED settings– Port mode– Keyboard type.v Mouse information includes:– Enabled or disabled– Sample rate– Resolut
Scan Pattern SetupPort/Sec Name6/20 Downtown5/20 Sales-A4/10 Sales-B1/10 MatchF2 for defaultsIf Name order was selected, the Port and Name columns wil
Note: Legal characters are A-Z, 0-9, and the dash character. Lowercase lettersare converted to uppercase. Press the Backspace key to delete anincorrec
6. EnterAvailable menu attributes:Setting Effect on Menu or Window AppearanceResolution Affects the size of the menu and windows as they appear on the
Setting Values and Effect on Flag AppearanceEnabled Flags Off = Flag does not appearPorts On = Flag shows the connected port numberNames On = Flag sho
Making connections under powerAdditional servers, can be connected to the selector switch while the selector switchis running.Failed devices such as a
Installing stabilizer bracketsSee the unpacking instructions that come with the rack cabinet for information onhow to unpack and locate the rack cabin
190 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service informationThese procedures are written with the assumption that you have model-specifictraining on all computers, or that are familia
1.PERIGOv O peso máximo permitido para dispositivos montados em trilhos é de80 kg (176 lbs). Não instale dispositivos em trilhos que excedam estepeso.
1.DANGER2.DANGER3.DANGER4.DANGERRelated service information 193
1.DANGERv Le poids maximal d’une unité montée sur glissières est de 80 kg ;n’installez pas d’unités dont le poids est supérieur.v Le centre de gravité
1.VORSICHTv Das zulässige Höchstgewicht für auf Schienen montierte Einheitenbeträgt 80 kg. Keine Einheiten mit höheren Gewicht einbauen.v Der Schwerpu
1.PERICOLOv Il peso massimo consentito per i dispositivi montati su slitte è di 80 kg.Non installare dispositivi scorrevoli che hanno un peso superior
1.2.3.4.Related service information 197
1.PELIGROv El peso máximo permitido para los dispositivos montados en correderas esde 80 Kg (176 lbs). No instale dispositivos deslizantes que excedan
v Japanesev Koreanv SpanishImportant: All caution and danger statements in this IBM documentation begin witha number. This number is used to cross ref
Installing the NetBAY42 stabilizer brackets:1. Use a 12 mm open-end wrench to lower each of the four leveling pads justenough so that they touch the f
v Statement 2CAUTION:When replacing the lithium battery, use only IBM Part Number 33F8354 or anequivalent type battery recommended by the manufacturer
v Statement 5CAUTION:The power control button on the device and the power switch on the power supply donot turn off the electrical current supplied to
Importante:Todas as instruções de cuidado e perigo da IBM documentation começam com umnúmero. Este número é utilizado para fazer referência cruzada de
v Instrução 2CUIDADO:Ao substituir a bateria de lítio, utilize apenas uma bateria IBM, Número de Peça 33F8354ou uma bateria de tipo equivalente, recom
v Instrução 4≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs)CUIDADO:Ao levantar a máquina, faça-o com segurança.v Instrução 5CUIDADO:Os botões Li
Related service information 205
206 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service information 207
208 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service information 209
4. If necessary, bolt the rack cabinet to the floor through the provided holes in thestabilizer brackets.Removing and installing NetBAY25 panelsThe Ne
210 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service information 211
Important:Toutes les consignes Attention et Danger indiquées dans la bibliothèque IBMdocumentation sont précédées d’un numéro. Ce dernier permet de me
v Notice n° 2ATTENTION:Remplacez la pile au lithium usagée par une pile de référence identiqueexclusivement - voir la référence IBM - ou par une pile
v Notice n° 4≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs)ATTENTION:Faites-vous aider pour soulever ce produit.v Notice n° 5ATTENTION:Le bouton
Wichtig:Alle Sicherheitshinweise in dieser IBM documentation beginnen mit einer Nummer.Diese Nummer verweist auf einen englischen Sicherheitshinweis m
v Hinweis 2ACHTUNG:Eine verbrauchte Batterie nur durch eine Batterie mit der IBM Teilenummer 33F8354 oderdurch eine vom Hersteller empfohlene Batterie
v Hinweis 4≥18 kg ≥32 kg ≥55 kgACHTUNG:Beim Anheben der Maschine die vorgeschriebenen Sicherheitsbestimmungen beachten.v Hinweis 5ACHTUNG:Mit dem Betr
Importante:Tutti gli avvisi di attenzione e di pericolo riportati nella pubblicazione IBMdocumentation iniziano con un numero. Questo numero viene uti
v Avviso 2ATTENZIONE:Quando si sostituisce la batteria al litio, utilizzare solo una batteria IBM con numero parte33F8354 o batterie dello stesso tipo
Removing rear filler panels: Use the following procedure to remove the rear fillerpanels from the rack cabinet:1. Grasp the rear filler panel firmly a
v Avviso 4≥18 kg ≥32 kg ≥55 kgATTENZIONE:Durante il sollevamento della macchina seguire delle norme di sicurezza.v Avviso 5ATTENZIONE:Il pulsante del
Related service information 221
222 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service information 223
224 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Related service information 225
226 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Importante:Todas las declaraciones de precauciín de esta IBM documentation empiezan conun número. Dicho número se emplea para establecer una referenci
v Declaración 2PRECAUCIÓN:Cuando desee sustituir la batería de litio, utilice únicamente el número de pieza 33F8354 deIBM o cualquier tipo de batería
v Declaración 4≥18 kg ≥32 kg ≥55 kgPRECAUCIÓN:Tome medidas de seguridad al levantar el producto.v Declaración 5PRECAUCIÓN:El botín de control de alime
Note: You do not need to remove the rear filler panels unless you are attaching therack cabinets to form a suite of rack cabinets.Removing and install
Consider these conditions and the safety hazards they present:v Electrical hazards, especially primary power (primary voltage on the frame cancause se
v Select a grounding system, such as those listed below, to provide protection thatmeets the specific service requirement.Note: The use of a grounding
CAUTION:Important:To eliminate confusion, identical systems are considered identical only if they:1. Are the exact machine type and model2. Have the s
Part Number: 10K2658(1P) P/N: 10K2658
Removing rear filler panels: Use the following procedure to remove the rear fillerpanels from the rack cabinet:1. Grasp the rear filler panel firmly a
2. Hold the filler panel fully against the side of the rack cabinet; then, slide the fillerpanel toward the rear of the rack cabinet. Ensure that both
Removing and installing rack doorsRemove the rack doors when installing and removing options in the rack cabinet. Allrack cabinets come with front and
Removing and installing a NetBAY42 door: Use the following procedure toremove a front or rear door from the rack cabinet:1. Unlock and open the door.2
Note: The illustrations in this procedure are of a NetBAY42 rack cabinet. The sameprocedure applies to the NetBAY25 rack cabinet.1. Remove the door ac
Ha rdw ar e M ain tenan ce Man u alIBMPCServer/EnterpriseRacksTypes 9306, 9308
4. Carefully rotate the door 180°; then, install the door on the other side of the rackcabinet.Figure 15. Rotating and installing the door20 Hardware
5. Remove the IBM logo from the bottom of the door; then, snap it into place nearthe top of the perforated section of the door.Figure 16. Moving the I
Attaching NetBAY42 Rack cabinets in a suiteExpansion rack cabinets come with all the hardware required for you to attach rackcabinets together and for
5. If required, move the rear-door-latch-bracket from the expansion rack cabinet tothe right side of a rack cabinet that does not have a rear filler p
DANGERv Plug power cords from devices in the rack cabinet into electrical outletsthat are located near the rack cabinet and are easily accessible.v Ea
Note: Make sure that the notch in the cable-management bracket points toward thefront of the rack cabinet when you install the bracket on the rack cab
DANGERv Plug power cords from devices in the rack cabinet into electrical outletsthat are located near the rack cabinet and are easily accessible.v Ea
Statement 11:CAUTION:Removing components from the upper positions in the rack cabinet improvesrack stability during relocation. Follow these general g
Part Listing (Type 9306)44145112116131516163210978Index Rack Enclosure (Type 9306) FRU1 42U Door (Models 420, 421) 06P60741 25U Door (Model 250) 32P10
Index Rack Enclosure (Type 9306) FRU14 25U x 600 x 1000 Rack Framework Only (Model 250) 32P101015 Swivel Caster (Models 250, 420, 421) 06P605516 Swive
Note:Before using this information and the product it supports, be sure to read the generalinformation under “Safety information” on page 191.Seventh
30 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Type 9306 Models 200/900/910Type 9306 Models 900/910FeaturesThe IBM NetBAY22, Type 9306, Model 200 Rack enclosure is a 22-U (1-U = 1.75inch) industry-
Parts Listing (Type 9306 Model 200)1235678941032 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Index Rack Enclosure (Type 9306 Model 200) FRU1 Top Cover including cover standoffs and screws 28L05482 Rear EIA Rail (1) includes mounting hardware 2
Rack Enclosure (Type 9306 Model 200) Options FRUHardware Kit for NetBAY Power Distribution Units 09N9671Flat Panel Monitor Rack Mount Kit (T54A, model
Perforated Doors (model 910)The Type 9306 Model 910 Rack comes with front and rear perforated doors thatprovide enhanced cooling and airflow for compo
2. If the front door is locked, unlock it; then, open the front door.Locked Unlocked3. While supporting the door, remove all four hinge pins that hold
®Note: Insert the screw through the bracket and into the lower of the two holesin the new center location.5. Remove the other hinge bracket 3 and st
Parts listing (Type 9306 Model 900/910)11011 2345678938 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Index Rack Enclosure (Type 9306 Model 900/910) FRU1 Top Cover including cover standoffs and screws 12J44812 Rear EIA Rail (1) includes mounting hardwa
ContentsAbout this manual ...viiImportant safety information ...viiOnline support ...viiGen
Rack Enclosure (Type 9306 Model 900/910) Options FRUConcentrator with Hardware (8 port) 76H4948Concentrator with Hardware (4 port) 28L05431x4 switch 0
Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TXFeaturesThe 9306 IBM PC Server Rack Enclosure, models 4QS, 9QS, 9TS come in threeprimary models.v 19-inch
ServerSelectorConsoleMonitorBezelServerSelectorCableServerSelectorElectronicsServerSelectorKeypadServer selector unitThe server selector unit is locat
ConnectionsMONOVGA1KBOVGA2VGA3VGA4VGA5VGA7VGA6VGA8MOUK1M1K2M2K3M3K4M4K5M5K6M6K7M7K8M8ServerMonitorConnectionsAC PowerInputServer SelectorUnit On-OffSw
CircuitBreakerAC Fuse115V ACPower-OnIndicator230V ACPower-OnIndicatorVoltageSelectionSwitchAC PowerOutputAC PowerInputCooling fanTo remove the cooling
strain-relieving clamp.GroundWirePowerPlugSliding traysModels 4QS and 4QX come with either single latch slide rails or dual latch sliderails. Single l
Dual latch rail trayTo remove a sliding tray with dual latch rails:1. Power-off the rack.2. Open the rear door of the rack cabinet and remove the pin
Note: You will need to adjust the position of the sliding rail in order to line up theaccess holes over the locations of the screws.Keyboard trayTo re
Parts listing (Type 9306 – 19-inch) Models 9QS, 9TS and 9QX, 9TXThis parts listing is for Models 9QS, 9TS and 9QX, 9TX15678910111213141516171819202221
Index 19-Inch Rack Enclosure (Type 9306) FRU1 Adapter Plate Options:PS/2 Server 85/95 76H3733Model 300 76H3734Model 500, 700 76H37342 Monitor Stand 07
Features ...73Locations ...73Casters...73Foot pads ...7
Index 19-Inch Rack Enclosure (Type 9306) FRU29 Dual Server Tray 76H038229 Dual Server Shelf 76H038530 Single Server Tray 76H038419-Inch Single Slide S
Parts listing (Type 9306 – 24-inch) Models 4QS, 4QXThis parts listing is for Models 4QS and 4QX.156789101112181920212223131415161723428293026272425Typ
Index 24-Inch Rack Enclosure (Type 9306) FRU1 Adapter Plate Options:PS/2 Server 85/95 76H3733Model 300 76H3734Model 500, 700 76H37352 Monitor Stand 07
Rack Enclosure Kits 24-inch (Type 9306) FRUBolt-Together Kit (19-Inch to 24-Inch, 24-Inch to 19-Inch) – includes: 19-InchAttachment Bracket (2 each);
54 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
NetBAY 42 Enterprise Rack (Type 9308 Models 42P, 42X, 4SA,4SB, 42S, 42E)FeaturesThe IBM NetBAY 42 Enterprise Rack (Type 9308 – Models 42P, 42X, 4SA, 4
Primary Rack (Model 42P)56 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Extension Rack (Model 42X)NetBAY 42 Enterprise Rack (Type 9308 Models 42P, 42X, 4SA, 4SB, 42S, 42E) 57
Primary Rack (42S)58 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Expansion Rack (42E)LocationsThe following sections contain information on specific equipment locations.The primary rack cabinet comes with side panel
NetBAY Power Distribution Units ...130NetBAY rack Power Distribution Unit introduction ...130Tool requirements ...
1. From the inside of the rear of the rack cabinet, slide the side panel locking bartoward the unlocked position.2. Push down the release latches and
1. On the top of the rack cabinet, loosen the four screws that hold each side panelin place.2. Tilt the side panel slightly toward you; then, remove i
Front and rear doors – Models 42P, 42X, 4SA, 4SBTo remove a door:1. Unlock the door and open it fully.2. Grasp the door 1 firmly with both hands and
Rear door – Models 42S, 42EUse the following procedure to remove a rear door from the rack cabinet:1. Unlock and open the rear door.2. Grasp the door
Hinge pinHinge pinlatchFront doorFigure 22. Removing a front door from the rack cabinet64 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
1. Unlock and open the front door.2. While supporting the door, lift the bottom hinge-pin latch and move it clockwiseto unlock the bottom hinge pin; t
3. Relocate your rack cabinet; then, install the top 6U portion of the rack cabinetusing all 16 of the screws that you removed.4. Remove both support
1. Remove both side panels (see “Removing and installing the side panels” onpage 59) from the side of a primary rack cabinet that is adjacent to anexp
5. Snap the trim pieces into place between the adjacent rack cabinets. Install onetrim piece in the front and one in the rear.6. Repeat step 3 through
Note: Use clip nuts if your rack has circular holes. If your rack has squareholes, you can use the rack-insertion tool or a flat-blade screwdriver toi
Grounding requirements ...231Problem determination tips ...231vi Hardware Maintenance Manual: IBM PC Server/Enterpri
6. Loosely insert one M5 screw 1 into each rail.Statement 5≥18 kg (37 lbs) ≥32 kg (70.5 lbs) ≥55 kg (121.2 lbs)CAUTION:Use safe practices when lifti
Parts listing (Type 9308 Model 42P, 42X)1234567Index Rack Enclosure (Type 9308 Model 42P, 42X, 4SA, 4SB, 42S, 42E) FRU1 Top Cover Assembly including c
Rack Enclosure (Type 9308 Model 42P, 42X, 4SA, 4SB, 42S, 42E) Options FRUC13 - NEMA 5-15P Power Cable 76H4962C19 - NEMA 5-15P Power Cable 12J4479Video
NetBAY3 enclosureFeaturesThe IBM NetBAY3 enclosure provides a convenient 3-U high by 24-inch deepstorage cabinet for the installation of computer devi
Foot padsFront cover74 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Rear panelNote: Make sure empty NetBAY3 enclosures (no devices installed) have the rearcover securely attached.NetBAY3 enclosure 75
Device side railsStacking NetBAY3 enclosuresNote: Make sure NetBAY3 enclosures in a stack are securely fastened together.76 Hardware Maintenance Manua
Note: The maximum server weight is 77 kg (170 lb.).NetBAY3 enclosure 77
Parts Listing (NetBAY3)1234Index NetBAY3 Enclosure (NetBAY3) FRU1 3-U Enclosure Frame 03K87972 Front Bezel Assembly with Lock and Keys 03K87983 Foot P
NetBAY3E enclosureFeaturesThe IBM NetBAY3E enclosure provides a convenient 3-U high by 28-inch deepstorage cabinet for the installation of computer de
About this manualThis manual contains diagnostic information, a Symptom-to-FRU index, serviceinformation, error codes, error messages, and configurati
Front cover80 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Rear panelNote: Make sure empty NetBAY3E enclosures (no devices installed) have the rearcover securely attached.Device side railsStacking NetBAY3E enc
Important:v Always lock the casters with the caster stabilizer bar before removingor installing any devices in or on the enclosure.v Always use the ca
Parts listing (NetBAY3E)1234Index NetBAY3E Enclosure (NetBAY3E) FRU1 3-U Enclosure Frame 28L05712 Front Bezel Assembly with Lock and Keys 03K87983 Cas
84 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
1U Flat Panel Monitor Console KitThe IBM NetBAY Flat Panel Monitor Console Kit is a flat panel monitor andkeyboard tray in one solution. An optional s
v Miscellaneous hardware kit (for attaching console switch brackets and installingthe keyboard tray in a rack cabinet)v Two self-adhesive hook-and-loo
Installing the Flat Panel Monitor Console KitThe Flat Panel Monitor Console Kit occupies 1U of rack mounting space in a rackcabinet. You can install a
1. Refer to the documentation that comes with your rack cabinet for additionalinformation.Notes:a. Removing rack doors and side panels might make inst
2. Place the tray on a stable flat surface; then, carefully cut the cable straps onthe cable-management arm and slide rail to release the bundled cabl